• RQJ/*/* F-QZFS* series axial flow shut-off valve
RQJ/*/* F-QZFS* series axial flow shut-off valve
+

RQJ/*/* F-QZFS* series axial flow shut-off valve

The RQJ/*/*F-QZFS series gas safety shut-off valves are axial flow structure safety shut-off valves. This series of products has a flow path direction that is consistent with the pipeline gas flow direction, featuring advantages such as high flow capacity, high precision, good sealing performance, and fast response speed. It can achieve overpressure and low-pressure protection functions. Applicable media: natural gas, artificial coal gas, liquefied petroleum gas, and other non-corrosive gases.
  • Commodity name: RQJ/*/* F-QZFS* series axial flow shut-off valve

Classification

Key Words

Product Overview

The RQJ/*/*F-QZFS* series gas safety shut-off valve is an axial flow structure safety shut-off valve. This series of products has a flow path direction consistent with the pipeline gas flow direction, featuring advantages such as large flow capacity, high precision, good sealing performance, and fast response speed, capable of achieving overpressure and low-pressure protection functions.
Applicable media: natural gas, artificial coal gas, liquefied petroleum gas, and other non-corrosive gases.

Technical Parameters

Maximum Allowable Pressure

≤10.0MPa

Connection Type

Flange connection DN25, DN50, DN80, DN100

Inlet Pressure Range

P1: ≤10.0MPa

Flange Rating

---PN25, PN100
---ANSI150 RF, ANSI300 RF, ANSI1300 RF

Overpressure Shut-off Setting Range

0.03~8.0MPa

Working Temperature

-20℃~60℃

Shut-off Accuracy

Up to AG1.0

   

Response Time

<=1 second

   

外形尺寸

 

切断阀型号

A

I

PN25

PN100

ANSI150

ANSI300

ANSI600

PN25

PN100

ANSI150

ANSI300

ANSI600

QZFS50

165

165

165

165

165

254

286

254

266.5

286

QZFS80

230

230

230

230

230

298.5

336.5

298.5

317.5

336.5

QZFS100

275

275

275

275

275

352.5

394

352.5

368.5

394

QZFS150

410

410

410

410

410

451

508

451

473

508

recommend products

Straight pipe section of the flow meter

The straight pipe sections installed before and after the flow meter can ensure that the fluid flow state in the pipeline is uniform, which does not directly affect the measurement accuracy of the flow meter, achieving good measurement results.

Quickly open the blind plate.

The quick-opening blind plate is a fixed quick-opening device set at the pipe opening for cleaning, unblocking pipelines, and inspecting and clearing containers.

Filters

过滤器

RQJ/*/* F-QZFS* series axial flow shut-off valve

The RQJ/*/*F-QZFS series gas safety shut-off valves are axial flow structure safety shut-off valves. This series of products has a flow path direction that is consistent with the pipeline gas flow direction, featuring advantages such as high flow capacity, high precision, good sealing performance, and fast response speed. It can achieve overpressure and low-pressure protection functions. Applicable media: natural gas, artificial coal gas, liquefied petroleum gas, and other non-corrosive gases.

Free access to more customized information

Note: Please leave your contact information and our professionals will contact you as soon as possible!

Submit immediately