• RQJ/*/*F-QZQS* series gas safety shut-off valve
RQJ/*/*F-QZQS* series gas safety shut-off valve
+

RQJ/*/*F-QZQS* series gas safety shut-off valve

The RQJ/*/*F-QZQS series gas safety shut-off valves are used in gas transmission and distribution systems. When the pressure of the pipeline controlled by the shut-off valve is higher or lower than the set shut-off pressure, the RQJ safety shut-off valve can urgently cut off the gas flow in the pipeline to protect downstream equipment. Applicable media: natural gas, artificial coal gas, liquefied petroleum gas, and other non-corrosive gases.
  • Commodity name: RQJ/*/*F-QZQS* series gas safety shut-off valve

Classification

Key Words

 

Product Overview

The RQJ/*/*F-QZQS* series gas safety shut-off valves are used in gas transmission and distribution systems. When the pressure of the pipeline controlled by the shut-off valve is higher or lower than the set shut-off pressure, the RQJ safety shut-off valve can urgently cut off the gas flow in the pipeline to protect downstream equipment.
Applicable media: natural gas, artificial coal gas, liquefied petroleum gas, and other non-corrosive gases.

Technical Parameters

Maximum Allowable Pressure

5.0MPa

Connection Type

Flange connection DN25, DN50, DN80, DN100

Inlet Pressure Range

P1: ≤5.0MPa

Flange Rating

--- PN16, PN25, PN40 (compliant with: HG20592-2009, raised face)
--- ANSI150 RF, ANSI 300 RF (compliant with: HG20615-2009, raised face)

Overpressure Shut-off Setting Range

0.003~4.0MPa

Signal Pipe Interface

NPT3/8”

Shut-off Accuracy

Up to AG2.5

Working Temperature

-20℃~60℃

Response Time

<=1 second

   

Dimensions

 

通径

尺寸(mm)

压力等级
PN16 PN25/PN ANSI 150 RF ANSI 300 RF

DN50

A

254 267 254 267

B

83

83

75

83

C

150

150

150

150

DN80

A

298 317 298 317

B

100

100

95

105

C

174

174

174

174

DN100

A

352

368

352

368

B

110 118 115 128

C

189 189 189 189

recommend products

Straight pipe section of the flow meter

The straight pipe sections installed before and after the flow meter can ensure that the fluid flow state in the pipeline is uniform, which does not directly affect the measurement accuracy of the flow meter, achieving good measurement results.

Quickly open the blind plate.

The quick-opening blind plate is a fixed quick-opening device set at the pipe opening for cleaning, unblocking pipelines, and inspecting and clearing containers.

Filters

过滤器

RQJ/*/* F-QZFS* series axial flow shut-off valve

The RQJ/*/*F-QZFS series gas safety shut-off valves are axial flow structure safety shut-off valves. This series of products has a flow path direction that is consistent with the pipeline gas flow direction, featuring advantages such as high flow capacity, high precision, good sealing performance, and fast response speed. It can achieve overpressure and low-pressure protection functions. Applicable media: natural gas, artificial coal gas, liquefied petroleum gas, and other non-corrosive gases.

Free access to more customized information

Note: Please leave your contact information and our professionals will contact you as soon as possible!

Submit immediately